Breakers on UK household circuits are designed to allow considerably more power than comparable breakers around the world.
That is utterly irrelevant. Circuit breakers and fuses are designed for the exclusive and sole purpose of protecting the circuit from being overloaded. A 100 amp circuit with a 100 Amp fuse is exactly as safe as a 20 amp circuit with a 20 amp fuse or a 5 amp circuit with a 5 amp fuse. If the voltage is above ~100-200V, all 3 of these are hundreds of times the amount of current it would take to deliver a fatal electric shock, and none of those fuses would trip from you getting shocked.
To protect humans from electric shock we use residual current devices, which trip at 10’s of Milli amps. And here’s actually an advantage of a ring circuit. It forces you to place RCD protection on every single outlet in the building, instead of skimping on costs by just putting it on the branches that legally require one, like bathrooms and kitchens.
Those fuses are not needed in Japanese (or North American, or most other) plugs. We don’t need to protect the “external wiring” separately from the household wiring: the household circuit breaker is rated lower than the “external wiring”. Drawing a direct short on the “external wiring” in a UK circuit is not sufficient to trip the UK circuit breaker in the UK distribution panel; they need a secondary current limiter (a fuse) to provide that function.
That’s just demonstrably untrue. An individual branch of a household circuits in both the US or Japan can easily be fused at 20A (fun fact: European branch circuis, because of the higher voltage that you were raging against in your first comment, can handle more electric load whilst having SMALLER 16A breakers). In both Japan and America you can buy extension cords rated for 10 or 15A. So no. You just told a straight up, unequivocal lie there. And a dead short on a 240V network will literally trip everything. UK ring circuits are fused at 30 Amps. A dead short at 240V with only the internal resistance of copper wiring would pull current in the neighborhood of 1000 amps. 1000, somewhat famously, being slightly larger than 30, making this another lie there.
And even if it weren’t a lie, how on earth does the location of the fuse make a difference in safety here ? If it’s in the wall or in the plug, as long as it’s there and does it’s job both would be equally safe.
The function provided by those shutters is achieved in the Japanese wiring by lower voltage, narrow holes in receptacles (allowable because they don’t need as large a contact to safely carry the lower rated current) and whole-house AFCI/GFCI.
No it isn’t. 110V is still dangerous to a child, and if you think otherwise I hope to god you aren’t, or ever become a parent. Also, as I stated, your plugs literally allow for an electric shock to happen whilst unplugging them because they’re so terrible. As for whole house GFCI, that is by necessity included in a ring circuit that wants GFCI on any outlet at all.
Also you seem to fundamentally misunderstand the relationship of current and voltage. For a given electrical appliance, with a given wattage, a lower voltage means it needs to draw more current, not less. That’s why the US Japan need to have 20A household breakers, whereas in the EU 16A branches are more than enough, whilst still providing a higher load handling capability than a 20A Japanese fuse. A 1000 Watt microwave plugged into a Japanese socket will draw over twice as much current as a 1000 Watt microwave plugged into an EU or UK socket (which also means it produces 4 times the amount of electrical waste energy as heat, though that is generally negligible for short household cable runs either way. Can make a difference on the scale of a country though).
And don’t think I didn’t notice you just quietly avoided responding to any of my arguments pointing out the obvious falsehoods in your voltage claim.
Frankly, at this point, all you’ve done is utterly convince me that you are totally and utterly unqualified to speak on this topic. Almost every claim you make is wrong. And not even just “slightly oversimplified/technically incorrect” wrong, just straight up demonstrably untrue.






Did you just deliberately ignore everything I wrote ? Both 20 and 100amps are several hundred times more current than it needs takes to kill you. And the resistance of your body is way to high to pass more than a few hundred milliamps anyway.
For a given voltage, the outcome of recieving a shock on a 20A fused circuit is literally indistinguishable and fully identical to that of receiving a shock on a 100A fused circuit. Identical. Literally.
No it isn’t. I literally just told you you can buy 15A rated extension cords in Japan in the comment you’re replying to. 15, is in fact less than 20, just fyi. Are you deliberately ignoring half of what I wrote ?
Wrong. Again. The current limit imposed by the internal resistance of your body at voltages in the range of 100-200 is a few hundred milliamps. Maybe an amp or two if you stick electrodes inside yourself, and anything higher than 100 going through your heart is lethal anyway. The power that will pass through your body depends exclusively and solely on the voltage. The capacity and fusing of the circuit is utterly irrelevant, unless it’s fused at like 40 MILLI amps.
Man I fucking love how you literally just picked out the first line in a comment pointing out another one of the things you said that are objectively untrue (a dead short not blowing a UK ring fuse) and ignore everything else in the comment. You must have seen the comment to quote part of it, and yet you ignore it entirely. You’re clearly and demonstrably not arguing in good faith.
That’s fucking rich, when I’ve literally explicitly addressed every single point you made, whilst you seemingly deliberately ignore half the ones I make. Literally repeating falsehoods I disproved in the comment you’re replying to, whilst you’re replying.